Quest Controls telecommunications control and monitoring Quest Controls telecommunications control and monitoring

Back To Home Page
TELSEC 2000E
Control, Monitoring & Alarming
System

Quest P/N 150629
The TELSEC 2000E™ Shelter Controller from Quest Controls provides direct digital control over all environmental control functions including access control of the main door. This compact unit enables operators of remote shelters to simultaneously reduce energy consumption, equipment operating costs and manpower requirements while providing a secure facility.

The Controller performs all control, monitoring and communications functions within a single unit. This level of sophistication makes it superior to electromechanical components, which often require two or three separate devices to accomplish the same task. The system is easily accessible, using the front panel, the craft port or a modem to make setpoint changes. The controller operates with a standard control program for the application or can be customized to meet your specifications. A lithium battery provides continuous backup for clock and system programming, eliminating the need to reprogram the unit or reset the clock after a power interruption.

Components Replaced by the TELSEC 2000E™
Air conditioning control thermostats
Lead/Lag controller for two AC units
High temperature alarm thermostat
Low temperature alarm thermostat
Exhaust fan thermostat
Mechanical lead/lag controller
High humidity alarm thermostat
Numeric combination door lock
Telect alarm strip deleted freeing up
space on rack
Intrusion bypass switch and enclosure
Significant reduction in conduit since
the items above are combined into one unit

TELSEC 2000E System Features:

• Controls two air conditioning units for Fan, Cooling, Heat
and Economizer
• Prewired Alarm outputs to a DB37 connector for high temperature,
low temperature, commercial power fail,
tower light alarms, fuse alarm, power plant alarms, smoke and
halon discharge
• Card Access control of main door with up to 500 cards per site
• Standard configuration controls, monitors and alarms inside
temperature and humidity
• Monitors outside air temperature for economizer control
• Intelligent Lead/lag control of AC units with programmable switch
time for 1-168 hours
• Occupied Mode - Ability to change setpoint to an occupied mode
with automatic reset. Time delay is user defined.
• Programmable settings for control and alarm setpoints with built-in
limits to prevent personnel from adjusting
the settings out of range
• Smoke detection input to shut down AC units on alarm
• Thirty-two character backlit LCD display for normal and
alarm status
• Eight-button keypad for adjusting setpoints and operating
conditions
• Built-in Craft Port supports ASCII protocol
• Industrial grade modem for alarm call-outs and status monitoring
• Any standard ASCII compatible communications software can
communicate with the system
• Supports two alarm phone numbers for calls to PCs and two
pager phone numbers
• Power supply options of +24 and -48 VDC

Specifications


Part Number: 150629 - Includes, modem, card reader, door actuator, inside/outside temp sensor and humidity sensor.
Inputs (16): Inside and outside temperature readings +/- 0.5°C. Inside and outside humidity sensor.
2% accuracy. Contact closures for power alarm, smoke, intrusion, tower lights and halon discharge.
Card Access: Supports industry standard card readers. Up to 500 cards can be programmed per site.
Outputs (24): 14 form A contact closure @ 1 Amp for AC unit control and alarm contacts. 10 form C contact closure @ 1 Amp.
Front Panel: Built-in programming panel with 8 keys and a 32-character display.
Modem: Supports 2400 Baud modem with AT command set.
Logging: All inputs and outputs are logged. Up to thirty days of data depending on configuration.
Software: Supports any off-the-shelf ASCII compatible communication package.
Electrical: +24 or -48 VDC 1 amp. max. Optional 120/220 VAC, 60Hz, 0.5 amp.
Battery:
Long life lithium. 10 year shelf, 1.5 years under load.
Environmental: Operating temperature 32 to 120 Degrees F
Storage temperature -40 to 250 Degrees F
0-95% RH Non-condensing
Dimensions: 13"W x 18.5"H x 2"D