GSM Gas Monitors:
Carbon Monoxide, Methane, & Hydrogen
Individual Gas Monitors for Vaults & RTs
[ Download 2 Page Brochure (128KB) ] |
Monitors Toxic or Combustible Gases
Stays Calibrated up to 5 Years without Drift
Field Adjustable Alarm Thresholds
Alarms for Gas Thresholds & Sensor Fault
Calibrates On-Site without Replacement
Visual LED Alarm Status |
|
|
Quests GSM Gas Monitors are designed to provide safe, reliable, and long life monitoring and alarming for toxic
and combustible gases for your underground vaults, CEVs, CEMHs, CUEs, CECs, and WICs. |
Monitors Carbon Monoxide (CO), Methane (HC), or Hydrogen (H2) Gases.
Microprocessor-based design enables gas monitors to stay in calibration up to 5 years; then can be calibrated on-site without replacing monitor.
Provides separate relays for exceeding pre-set gas thresholds and sensor failure.
Alarm thresholds adjustable 0 to 90% in the field via RS232 port.
Powered by 48VDC ensures gases are being monitored during commercial AC power failure.
Connect directly to the TELSEC® controllers. |
|
 |
Key Features
LED indicators exhibit power, alarm and sensor fault status.
Automatic reset when gas levels fall below alarm thresholds.
Communicate via RS232 port using standard, off-the-shelf
terminal emulation software, such as Procomm® or Hyperterminal®. |
|
Specifications
|
|
Sensor Description
|
Carbon Monoxide
(Toxic)
|
Methane
(Combustible) |
Hydrogen
(Combustible) |
Model#
|
GSM-CO |
GSM-HC |
GSM-H2 |
Part#
|
300151 |
300149 |
300148 |
| PID/SSI# |
001537000 |
N/A |
001537018 |
| Material ID# |
828371 |
N/A |
828372 |
| Detection Range |
0 to 250ppm |
0 to 10,000ppm |
0 to 500ppm |
Pre-set Alarm Level
|
50ppm |
5,000ppm |
200ppm |
Outputs
Relay Contact Rating
K1
K2
|
0.6 Amps at 125VAC or 2.0 Amps at 30VDC (resistive)
SPDT, Form C, normally de-energized for alarm
SPDT, Form C, normally energized for sensor fault
|
Accuracy
|
±5% FS (Full Scale) |
RS232 Port
|
db9: On-site calibration, retrieval of gas values, and adjustment of threshold alarms
|
Connections
|
12(305mm) wiring harness interfaces power and alarm relay
|
| Power |
10 to 60 VDC or 10 to 42 VAC, 3 Va
|
Electrical Compliance
|
Meets CSA standards (ENTELA Certifcation)
|
Ambient Operating Temp
|
0 to 110ºF (-18 to 43ºC) |
32 to 110ºF (0 to 43ºC) |
32 to 110ºF (0 to 43ºC) |
Dimensions
|
5.5(140mm) W X 5.5(140mm) H X 4.5(114mm) D |
Weight
|
1.8 lbs (0.8kg)
|
Warranty
|
1 year |
| Specifications are subject to change without notice |
|
Send mail to info@questcontrols.com with questions or comments about this web site.
Copyright©1999-2008 Quest Controls, Inc. Updated: 03.10.08
|
|
|