Quest Controls telecommunications control and monitoring
Quest Controls telecommunications control and monitoring
telecommunications control and monitoring
telecommunications control and monitoring
CGSM100 & CGSM300
Combined Gas Monitors for Vaults & RT’s

[ Download 2 Page Brochure (132KB) ]
• Monitors Toxic & Combustible Gases
• Accessible Real-time Gas Level Value (ppm)
• Field Adjustable Alarm Thresholds (ppm)
• Integrated Vent Fan Control
• Audible & Visual LED Alarm Status

The CGSM100 and CGSM300 are designed to provide safe, reliable, and long life
monitoring and alarming for toxic and combustible gases for your underground
vaults, CEVs, CEMHs, CUEs, CECs, and WICs.
• Monitors Carbon Monoxide (CO), Methane (HC), and Hydrogen (H2) (optional) Gases.
• Provides separate relays for sensor failure, carbon monoxide, combustible, hydrogen
(optional), and ventilation fan plus remote indicator output.
• Provides audible and visual alarms.
• Alarm thresholds adjustable 0 to 90% in the field via RS232 port.
• Powered by –48VDC ensures gases are being monitored during commercial AC power failure.
• CGSM100 comes in a stand-alone package and connects with the TELSEC® controllers.
• CGSM300 provides direct replacement for Sierra Monitor 2400 Vault Gas Monitor.
• CGSM300 supplies power to optional smoke detector as well as pass-thru alarms via
24-pin Amphenol Connector.

Key Features
• LED indicators exhibit alarm and sensor status for each sensor.
• Fault status LED indication turns on when a sensor becomes defective.
• Automatic reset when gas levels fall below alarm thresholds.
• Reset button silences audible alarm.
• Test button simulates alarm condition and performs system test diagnostics.
• Communicate via RS232 port using standard, off-the-shelf
terminal emulation software, such as, Procomm® or Hyperterminal®.



Carbon Monoxide Sensor (CO): 25 to 500 ppm operating range; factory set to 35 ppm.
Methane Sensor (HC): 1,000-10,000 ppm operating range; factory set at 5,000 ppm.
Hydrogen Sensor (H2) (Option): 1,000-10,000 operating range; factory set to 5,000 ppm.
Remote hydrogen gas sensor for CGSM100 CGSM300 gas monitors
Remote Hydrogen Gas Sensor option with 25'(7.5M) cable

Specifications
Description
Stand-alone Gas Monitor
(interfaces with TELSEC
®)
Direct Replacement for Sierra Monitor 2400
Model#
CGSM100 CGSM300
Part#
300150 300152
PID/SSI# 001536986 001536994
Material ID# 828369 828370
Option For Remote Hydrogen Gas Monitor option, order part# 300652 (includes 25'(7.5M) cable)
Smoke Detector Peripheral Low profile, self-diagnostic, 4-wire photoelectric with built-in sounder, order part# 300136
Outputs
Relay Contact Rating
K1
K2
K3
K4
K5

SPDT normally de-energized for CO sensor alarm. 10 Amps, 1/8 H.P., 277VAC (Resistive)
SPDT normally de-energized for HC sensor alarm. 10 Amps, 1/8 H.P., 277VAC (Resistive)
SPDT normally de-energized for optional H2 sensor alarm. 10 Amps, 1/8 H.P., 277VAC (Resistive)
DPDT normally de-energized for power/sensor fault. 5 Amps, 1/8 H.P., 277VAC (Resistive)
DPDT normally de-energized for Ventilation fan control common to all active sensors.
One of the C contacts common leg on K5 is fused with a 4-amp socketed micro fuse.
5 Amps, 1/8 H.P., 277VAC (Resistive)
DC Power Output
+12VDC and ground (max power 60mA) for remote Smoke Detector
RS232 Port
On-site calibration, retrieval of calibration values, and adjustment of threshold alarms
Connections
CGSM300: 24-pin Mil-Spec Amphenol Connector conveys alarm status and control outputs
Power 10 to 60VDC or 17 to 42VAC, 6 Va
Audible Alarm 80dB at 1M
Electrical Compliance
Meets CSA standards (ENTELA Certification)
Ambient Operating Temp
32 to 110ºF (0 to 43ºC)
Dimensions-CGSM
8.7"(221mm) H X 8.3"(211mm) W X 4.2"(107mm) D
Dimensions-H2 Sensor 4"(102mm) H X 3"(76mm) W X 1.75"(45mm) D
Weight-CGSM 4 lbs (1.8kg)
Weight-H2 Sensor 1 lb (0.45kg)
Warranty
1 year
Specifications are subject to change without notice


Send mail to info@questcontrols.com with questions or comments about this web site.