| TYPICAL CONFIGURATION FOR EQUIPMENT HUT |
| DIGITAL OUTPUTS |
1
|
AC UNIT 1 FAN CONTROL |
9 |
|
2
|
AC UNIT 1 COOL CONTROL |
10 |
|
| 3 |
AC UNIT 1 HEAT CONTROL |
11 |
|
| 4 |
AC UNIT 2 FAN CONTROL |
12 |
|
| 5 |
AC UNIT 2 COOL CONTROL |
13 |
|
| 6 |
AC UNIT 2 HEAT CONTROL |
14 |
|
| 7 |
VENT FAN CONTROL |
15 |
|
| 8 |
DOOR ACCESS CONTROL |
16 |
|
|
|
| UNIVERSAL INPUTS |
| # |
Input Name |
Sensor Type |
# |
Input Name |
Sensor Type |
| 1 |
HUT TEMPERATURE |
TEMP ºF |
17 |
LITE SPAN CRITICAL ALARM
|
DRY CONTACT |
| 2 |
HUT HUMIDITY |
%RH |
18 |
LITE SPAN MAJOR ALARM |
DRY CONTACT |
| 3 |
DC POWER PLANT VOLTAGE |
VDC |
19 |
LITE SPAN MINOR ALARM |
DRY CONTACT |
| 4 |
OUTSIDE AIR TEMPERATURE |
TEMP ºF |
20 |
|
|
| 5 |
VENT FAN PROOF OF RUN |
DRY CONTACT |
21 |
BATTERY STRING TEMPERATURE 1 |
TEMP ºF |
| 6 |
INTRUSION - DOOR MONITOR
|
DRY CONTACT |
22 |
BATTERY STRING VOLTAGE 1 |
VDC |
| 7 |
SMOKE/FIRE DETECTOR
|
DRY CONTACT |
23 |
BATTERY STRING TEMPERATURE 2 |
TEMP ºF |
| 8 |
SMOKE DETECTOR FAILURE
|
DRY CONTACT |
24 |
BATTERY STRING VOLTAGE 2 |
VDC |
| 9 |
COMMERCIAL POWER FAIL
|
DRY CONTACT |
25 |
BATTERY STRING TEMPERATURE 3 |
TEMP ºF |
| 10 |
HALON DISCHARGE MONITOR
|
DRY CONTACT |
26 |
BATTERY STRING VOLTAGE 3 |
VDC |
| 11 |
RECTIFIER MAJOR ALARM
|
DRY CONTACT |
27 |
BATTERY STRING TEMPERATURE 4 |
TEMP ºF |
| 12 |
RECTIFIER MINOR ALARM
|
DRY CONTACT |
28 |
BATTERY STRING VOLTAGE 4 |
VDC |
| 13 |
FUSE FAILURE MAJOR ALARM
|
DRY CONTACT |
29 |
|
|
| 14 |
FUSE FAILURE MINOR ALARM
|
DRY CONTACT |
30 |
|
|
| 15 |
MUX FAILURE MAJOR ALARM |
DRY CONTACT |
31 |
|
|
| 16 |
MUX FAILURE MINOR ALARM |
DRY CONTACT |
32 |
|
|
|
|
| ADDITIONAL EQUIPMENT |
| 1. CARD ACCESS READER WITH KEYPAD MOUNTED TO THE OUTSIDE OF THE HUT |
|
|
|
|