Quest Controls telecommunications control and monitoring
Quest Controls telecommunications control and monitoring
telecommunications control and monitoringtelecommunications control and monitoring
TYPICAL CONFIGURATION FOR CEV
DIGITAL OUTPUTS
1 VENT FAN 9 EMERGENCY LIGHTS
2 OUTSIDE AIR DAMPER 10 AUDIBLE ALARM (HORN)
3  AIR CONDITIONER #1 11 RED WARNING LIGHT CONTROL
4  AIR CONDITIONER #2 12 GREEN WARNING LIGHT CONTROL
5  HEATER 13 HATCH/DOOR CONTROL
6  DEHUMIDIFIER 14  
7  SUMP PUMP 15  
8  WORK LIGHTS 16  

UNIVERSAL INPUTS
# Input Name Sensor Type # Input Name Sensor Type
1 CEV TEMPERATURE TEMP ºF 17 LIGHT (OCCUPIED) MONITOR DRY CONTACT
2 CEV HUMIDITY %RH 18 RECTIFIER MAJOR ALARM DRY CONTACT
3 DC POWER PLANT VOLTAGE VDC 19 RECTIFIER MINOR ALARM DRY CONTACT
4 OUTSIDE AIR TEMPERATURE TEMP ºF 20 FUSE FAILURE MAJOR ALARM DRY CONTACT
5 VENT FAN PROOF OF RUN DRY CONTACT 21 FUSE FAILURE MINOR ALARM DRY CONTACT
6 INTRUSION - DOOR MONITOR DRY CONTACT 22 MUX FAILURE MAJOR ALARM DRY CONTACT
7 EXPLOSIVE GAS SENSOR DRY CONTACT 23 MUX FAILURE MINOR ALARM DRY CONTACT
8 TOXIC GAS SENSOR DRY CONTACT 24 LITE SPAN CRITICAL ALARM DRY CONTACT
9 SMOKE/FIRE DETECTOR DRY CONTACT 25 LITE SPAN MAJOR ALARM DRY CONTACT
10 SMOKE DETECTOR FAILURE DRY CONTACT 26 LITE SPAN MINOR ALARM DRY CONTACT
11 COMMERCIAL POWER FAIL DRY CONTACT 27 FUTURE USE  
12 GAS DETECTOR FAILURE DRY CONTACT 28 FUTURE USE  
13 MOISTURE SENSOR DRY CONTACT 29 BATTERY STRING TEMPERATURE 1 TEMP ºF
14 HIGH WATER FLOAT DRY CONTACT 30 BATTERY STRING TEMPERATURE 2 TEMP ºF
15 SUMP PUMP HIGH FLOAT DRY CONTACT 31 BATTERY STRING TEMPERATURE 3 TEMP ºF
16 SUMP PUMP LOW FLOAT DRY CONTACT 32 BATTERY STRING TEMPERATURE 4 TEMP ºF

ADDITIONAL EQUIPMENT
1. CARD ACCESS READER WITH KEYPAD MOUNTED TO THE OUTSIDE OF THE CEV